Cooling Tower Evaporation & Makeup Water Calculator
Calculate evaporation rate, blowdown, makeup water requirements, and annual water & chemical costs for cooling tower systems.
Tower Operating Parameters
GPM
Temperature drop across the tower (hot water in minus cold water out)
cycles
Typical: 3–6 for untreated makeup; 6–10 for softened/RO water
% of recirc
Modern towers: 0.001–0.005%; older towers: up to 0.02%
hrs/day
Water Balance Results
Evaporation Rate
--
Blowdown Rate
--
Drift Loss
--
Total Makeup Water
--
Daily Makeup Volume
--
Annual Water Consumption
--
Formulas Used
Evaporation (GPM) = Recirculation Rate × ΔT(°F) × 0.001
Blowdown (GPM) = Evaporation / (Cycles of Concentration − 1)
Drift (GPM) = Recirculation Rate × Drift% / 100
Makeup (GPM) = Evaporation + Blowdown + Drift
Water & Chemical Cost Estimate
$ / 1,000 gal
$ / 1,000 gal
Applied to blowdown volume only
$ / 1,000 gal makeup
Annual Cost Estimate (365 days)
Annual Water Cost
--
Annual Sewer Cost
--
Annual Chemical Cost
--
Total Annual Cost
--