The 24-125-13-a.FLA from ForeverPure Power is a 48 Volt, 1200 Ah tubular flooded lead-acid deep-cycle battery for renewable energy storage. Built with lead-antimony tubular positive plates, envelope separators, tank-formation curing, and Hardigg impact-resistant jars, this battery is engineered for long float-service life and deep daily cycling in renewable-energy systems. Each cell is rated for 1,500+ cycles at 80% depth of discharge and manufactured to Battery Council International (BCI) BCIS-14 capacity-test standards. Ideal for off-grid solar, hybrid solar/wind, battery-backup, telecom, and stationary renewable-energy storage.
- Tubular positive plates with lead-antimony alloy for deep-cycle durability
- Envelope separators (polyethylene) prevent short circuits and improve acid circulation
- Tank formation curing for uniform cell capacity and longer cycle life
- Bottom bridge construction strengthens plate-to-strap connection and resists shedding
- Hardigg (or equivalent) jar with high impact resistance and chemical stability
- Flip vent caps with integrated electrolyte level indicator
- Single-point watering system compatible (Flow-Rite / Philadelphia Scientific)
- 1,500+ cycles at 80% DoD — exceeds BCI life-cycle minimum
- 6 positive plates / 7 negative plates per cell (13 total plates), 24 cells
- Designed and tested to BCI BCIS-14 (Rev. 2011) performance standard
| SKU / Model | 24-125-13-a.FLA |
| Manufacturer Part Number (MPN) | 24-125-13-a.FLA |
| Brand | ForeverPure Power |
| Product Type | Tubular Flooded Lead-Acid Deep-Cycle Battery for Renewable Energy Storage |
| Chemistry | Flooded Lead-Acid (FLA), Tubular Positive Plate |
| Nominal Voltage | 48 Volt (24 cells × 2 V) |
| Rated Capacity | 1200 Ah at 20-hour rate |
| Capacity (6-hour reference) | 750 Ah @ 6 hr |
| Plates per Cell | 13 total (6 positive, 7 negative) |
| Cycle Life | 1,500+ cycles at 80% depth of discharge |
| Float Service Life | 15–20 years at 25°C (77°F) |
| Dimensions (W × D × H) | 20.38" W × 38" D × 30.5" H |
| Weight | 2771 lbs |
| Electrolyte | Dilute Sulfuric Acid (H₂SO₄), 1.280 SG fully charged (±0.010) |
| Terminal Type | Lead, bolt-on (top-post standard; side-terminal on request) |
| Warranty | 1-Year Limited Manufacturer Warranty |
Recommended charger voltage setpoints for a 48V system:
- Absorption: 56.4–58.8 V (constant voltage, stage 2)
- Float: 52.8–54.7 V (long-term maintenance, stage 3)
- Equalization: 60.0 V (2.50 V/cell, 2–4 hours, monthly or when cell SG spread ≥ 0.030)
- Discharge cutoff: 40.80 V (cutoff) per BCI
Watering:
- Use only distilled or deionized water — never tap water, well water, or acid
- Always water after a complete charge (prevents spill-over as electrolyte expands)
- Maintain level ≈ 0.25" below the bottom of the vent well, above the element protector
- Single-point watering system (Flow-Rite, Philadelphia Scientific) strongly recommended
Operating guidance:
- Do not discharge below 50% SoC for daily cycling / 80% occasionally — SG 1.140–1.160
- Match charger to battery: voltage, Ah, and type — keep Ah variance < 10%
- Target duty cycle: 70% discharge, 6–8 h charge, 4 h cool-down before use
- If battery exceeds 115°F (46°C) during charge, inspect for damage or overcharge
- Check specific gravity of a pilot cell monthly with a temperature-compensated hydrometer
- Keep terminals clean, torqued, and protected with corrosion-inhibiting compound
- Inspect the battery for damage, leaks, or shipping-acid residue before installation.
- Verify tray/compartment fit against published dimensions: 20.38" W × 38" D × 30.5" H. Confirm counterweight requirement (battery weight: 2771 lbs) for the rack or enclosure.
- Confirm correct voltage and polarity against the inverter/charge controller nameplate.
- Use a rated battery-lifting beam with insulated hooks — never single-point or chain-sling.
- Clean terminals, apply anti-corrosion compound, and torque connector hardware to manufacturer spec.
- Ensure adequate ventilation — hydrogen gas becomes explosive at 4% concentration.
- Commission with an initial equalize charge; record baseline voltage, SG, and temperature for each cell.
| UN Number | UN 2794 |
| Proper Shipping Name | Batteries, wet, filled with acid, electric storage |
| Hazard Class | 8 (Corrosive) |
| Packing Group | III |
| Label Required | Class 8 Corrosive |
| NMFC Code | 60680, Sub 1 |
| Freight Class | 70 |
| Handling | Keep upright. Non-stackable. White-glove / lift-gate available on request. |
ForeverPure Power flooded lead-acid batteries comply with OSHA 29 CFR 1910.1200 (HazCom 2012 / GHS), published per ANSI Z400.1 / Z129.1 and IMDG requirements.
- Primary hazards: Sulfuric acid (corrosive), lead compounds (IARC 2A carcinogen), hydrogen gas (flammable) generated during charging.
- PPE: Acid-resistant apron, face shield, chemical goggles, neoprene gloves, ventilated room.
- First aid: Flush skin/eyes with water for 15 minutes; seek medical attention immediately for acid contact.
- Spill response: Neutralize with sodium bicarbonate; dispose per local hazardous-waste regulation.
Available technical documents:
Lead-acid batteries are the most recycled consumer product in the United States, with a recycling rate above 99% (EPA, Battery Council International). The lead, polypropylene case, and sulfuric acid are all reclaimed at EPA-permitted secondary smelters and reused in new batteries.
- Federal law: Regulated under Universal Waste Rule (40 CFR Part 273) and RCRA hazardous-waste rules.
- State rules: Most US states require retailers and distributors to accept spent lead-acid batteries for recycling (the "Battery Act").
- Core charge: A refundable core charge may apply at purchase; returned cores are credited when received.
- Do not dispose in regular trash or with general recycling — this is prohibited in all 50 states.
- ForeverPure Corporation accepts spent FLA batteries for return and recycling. Contact us for a prepaid return label and core credit.
1-Year Limited Manufacturer Warranty against defects in materials and workmanship from date of shipment.
Coverage requires:
- Proper installation on compatible equipment of matching voltage and capacity
- Charging with a matched, approved flooded-lead-acid charger
- Documented watering with distilled/deionized water (monthly checks)
- Discharge not exceeding 80% DoD (SG above 1.140)
Exclusions: Physical damage, freezing, chronic undercharging or overcharging, sulfation from long-term storage without maintenance, tampering with vents or cells, or use outside of the rated duty cycle.
Q: What discharge rate is the 24-125-13-a.FLA rated at?
A: Renewable-energy storage batteries (.FLA suffix) are rated at the 20-hour discharge rate: 1200 Ah @ 20 hr. The forklift-duty twin of this battery is 750 Ah @ 6 hr (BCI BCIS-14).
Q: Is the 24-125-13-a.FLA a sealed (AGM/Gel) or flooded battery?
A: It is flooded (vented), tubular lead-acid. It requires periodic watering with distilled water and adequate room ventilation during charging. It is not sealed, AGM, or gel.
Q: How do I ship a wet/filled lead-acid battery?
A: It ships as UN 2794, Hazard Class 8 (Corrosive), NMFC 60680, Freight Class 70 via hazmat-certified LTL carrier, upright and non-stackable. We provide the shipping documentation; residential / lift-gate / inside delivery is quoted at checkout.
Q: How long will this battery last?
A: In renewable-energy float + daily cycling (30–50% DoD typical), expect 15–20 years of service life. Aggressive cycling to 80% DoD yields 1,500+ cycles (~5–7 years daily).
Q: What is the correct charger for the 24-125-13-a.FLA?
A: A 48V flooded-lead-acid charger matched to the battery's Ah capacity (within 10%), with 3-stage (bulk / absorption / float) profile and a monthly equalization setting at 60.0 V.
Q: Can I recycle the 24-125-13-a.FLA when it's end-of-life?
A: Yes. Lead-acid batteries are 99% recyclable. Return the spent battery to ForeverPure or any retailer accepting lead-acid cores for recycling. We issue a refundable core credit.
Need a freight quote, compatibility check, or bulk pricing? Contact ForeverPure or call (408) 969-2688.
Looking at 48V 1200 Ah @ 20 hr? You might also consider:
- 24-85-19.FLA — 48V, 1224 Ah @ 20 hr
- 24-85-17.FLA — 48V, 1088 Ah @ 20 hr
- 24-85-21.FLA — 48V, 1360 Ah @ 20 hr
Forklift twin:
Useful resources: